When you are planning a new lift or reviewing an existing installation you will quickly encounter terms like evacuation lift and firefighting lift. They sound similar and both relate to fire but they are designed for very different purposes under different technical standards.
For commercial building owners, facilities managers and designers understanding the difference is critical. It affects how people can be evacuated, how firefighters will use the building and what you need to consider at design stage or during a major lift modernisation.
This article explains in practical terms how an evacuation lift differs from a firefighting lift, how current UK and European standards approach each and what that means for your building. It is general guidance only and is not a substitute for fire engineering advice, building control input or consultation with your local fire and rescue service.
Evacuation lift vs firefighting lift: the simple definition
What is an evacuation lift?
An evacuation lift is a passenger or goods-passenger lift that is specifically designed and protected so it can be used as part of a managed evacuation strategy, typically to help people who cannot use stairs safely to leave the building in an emergency.
The concept is set out in standards in the BS EN 81 series dealing with the evacuation of persons with disabilities using lifts. These documents add requirements on top of the general lift safety rules in BS EN 81‑20 for passenger and goods-passenger lifts.
Key ideas behind an evacuation lift include:
- The lift and its associated equipment are protected from fire and smoke for the duration of the planned evacuation
- There is a fire and smoke protected safe area in front of the lift at the evacuation floor or floors so people have a place of relative safety while waiting to board or after exiting the car
- The lift is integrated into the overall evacuation strategy and building management systems, including arrangements for suspending service if conditions become unsafe
In plain language it is a lift that is purposely designed to move people out of the building under control during a fire or other emergency instead of being automatically taken out of service.
What is a firefighting lift?
A firefighting lift (sometimes called a firefighters lift or historically a fireman’s lift) is a lift specially designed so that the fire and rescue service can take control of it and use it as a tool for firefighting and rescue operations inside the building.
The technical requirements are covered in BS EN 81‑72, which sits alongside BS EN 81‑20 and specifies additional measures for lifts intended for use by firefighters.
A firefighting lift allows crews to travel rapidly with equipment to upper floors, often above the fire, and to move casualties or equipment vertically within the protected lift shaft. It is not provided for the general public to escape and guidance generally makes clear that it should not be treated as an escape route.
The core difference
The simplest way to think about it is:
- Evacuation lift: designed for managed evacuation of building occupants, especially those with impaired mobility, as part of the building’s escape strategy
- Firefighting lift: designed as a protected transport system for the fire and rescue service to access and fight the fire, then potentially to carry out rescues
Both are heavily dependent on the building’s fire strategy, power supplies and management arrangements but they have quite different primary users and control philosophies.
How standards approach evacuation lifts and firefighting lifts
Relevant standards and guidance
For most commercial buildings in the UK you will encounter some or all of the following when specifying or reviewing lifts that relate to fire:
- BS EN 81‑20 – general safety rules for construction and installation of passenger and goods-passenger lifts
- BS EN 81‑72 – additional requirements for firefighters lifts
- BS EN 81‑73 – rules for behaviour of lifts in the event of fire, for example recall of ordinary lifts to a safe floor
- BS EN 81‑76 – evacuation of persons with disabilities using lifts, commonly known as the evacuation lift standard
- Fire safety design guidance such as BS 9999 and government-approved documents, which discuss when lifts may be used for evacuation and refer to both evacuation lifts and firefighters lifts
These documents interact and are updated over time. There has been particular recent activity around evacuation lifts and means of escape for disabled people, including research for the UK government on the use of lifts for evacuation.
The important point for building owners is that the choice, design and approval of an evacuation lift or firefighting lift cannot be made in isolation. It must tie back to your building’s fire strategy, any fire engineered solutions and the relevant national regulations in force at the time of design or refurbishment.
Key design features of an evacuation lift
The detailed technical requirements belong with your lift consultant, fire engineer and design team but some of the main concepts behind a compliant evacuation lift are below.
1. Protected lift shaft and safe areas
An evacuation lift relies on the lift well, machinery spaces and associated lobbies or safe areas being protected against fire and smoke for long enough to carry out the planned evacuation.
This usually means:
- A fire resisting structure around the shaft to at least the level required by the building’s fire strategy
- Measures to limit smoke ingress, potentially including lobby design, smoke control or pressurisation systems where appropriate
- A designated safe area in front of the lift car with adequate space to accommodate wheelchair users or groups of people waiting safely for the lift
2. Reliable power and automatic rescue
Standards for evacuation lifts place strong emphasis on secure and reliable power supplies, often including both a primary and secondary supply so the lift can continue operating safely during an emergency.
Where a secondary power supply is not available there are usually provisions for an automatic rescue operation, which moves the lift car to a landing in a controlled way following a power failure and allows passengers to exit.
3. Integration with the building’s evacuation strategy
An evacuation lift is not intended to be an ordinary passenger lift that people simply choose to use or ignore in a fire. It forms part of a specific evacuation plan.
That plan may provide for:
- Automatic or managed prioritisation of certain floors, for example levels with larger numbers of mobility-impaired occupants
- Use under local management or with trained evacuation assistants
- Suspension of service if smoke or fire conditions at the safe area make further runs unsafe
Current practice in the UK tends to favour managed use with trained staff as part of personal emergency evacuation plans and general evacuation procedures.
4. Controls and communication
Evacuation lifts usually feature enhanced controls and communication compared with ordinary passenger lifts, which may include:
- Dedicated evacuation lift switches or key controls
- Clear indication of evacuation mode status
- Two-way communication between the car and a control point or monitoring centre
- Audible and visual information for users who may be anxious or have sensory impairments
The exact configuration should be agreed between the building owner, design team, fire engineer and lift installer in line with the chosen standard and fire strategy.
Key design features of a firefighting lift
Firefighting lifts share some concepts with evacuation lifts, such as protected shafts and robust power supplies, but the emphasis is on the needs of the fire and rescue service.
1. Protected well, lobby and machine spaces
BS EN 81‑72 requires that the lift well and the lift environment restrict the ingress of fire, heat and smoke and that the level of fire protection is at least equivalent to the main building structure.
Typically this involves:
- Fire resisting structure around the well and machine spaces
- Fire resisting lobbies giving access to the lift at each served floor
- Measures to control water entering the shaft from firefighting hoses, including defined maximum water levels in the pit
2. Firefighters’ controls
The car and landing controls are designed for use by trained firefighters, not the public. Features usually include:
- A firefighters’ switch or key-operated control which places the lift under the sole control of the fire service
- Car controls that allow firefighters to override landing calls
- Door controls so doors remain closed until firefighters deliberately open them, helping to limit smoke spread
3. Reliable power and emergency operation
Firefighting lifts are expected to have a secure primary supply and a suitably protected secondary supply or other arrangement that allows continued operation during an emergency.
As with evacuation lifts, the cabling and distribution for the lift’s power and control systems are generally protected to a fire resistance level consistent with the structural fire protection of the lift shaft.
4. Communication and emergency features
Firefighting lifts typically include:
- Two-way communication between the car and the firefighting control point
- Car lighting and emergency lighting suitable for use in smoky conditions
- Car dimensions and door sizes that allow firefighters with equipment, stretchers or casualties to be accommodated
In many high-rise or complex buildings there will also be a dedicated firefighters’ control panel at the fire service access level which brings together controls for the lift, smoke control and other life safety systems.
Can a lift be both an evacuation lift and a firefighting lift?
Some modern standards and guidance recognise that in appropriate circumstances a single lift installation can serve both as a firefighters lift and as part of a managed evacuation strategy, providing it is designed to meet the requirements for each use.
This is not simply a matter of labelling an existing firefighting lift as an evacuation lift. To function as both, the lift and building need to satisfy all relevant criteria, including:
- Suitable safe areas and evacuation routes for people using the lift
- Management procedures to avoid conflict between evacuation use and fire service operations
- Clear priorities embedded in the building’s fire strategy, for example how the lift’s control mode changes when the fire and rescue service arrives
Whether a combined arrangement is acceptable depends on the building type, height, occupancy, management arrangements and the view of the approving authorities. Project-specific advice from a competent fire engineer and early engagement with building control and the local fire and rescue service are essential.
What building owners and managers should consider
If you own or manage a commercial building you are unlikely to design the lift system yourself. However, the decisions you make early on will strongly influence whether an evacuation lift, a firefighting lift or both are appropriate.
1. What does your fire strategy require?
Your fire strategy should set out how people will escape or be evacuated in different fire scenarios, including those who cannot use stairs unaided. On that basis the design team and fire engineer can determine whether lifts are needed for evacuation and if so what performance they must achieve.
Current guidance in the UK accepts that lifts can form part of an evacuation strategy for disabled people but emphasises that they must be specifically designed, protected and managed for that purpose. An ordinary passenger lift that simply responds to fire recall is not an evacuation lift.
2. Do you already have a firefighting lift?
Many taller commercial and residential buildings already incorporate a firefighting lift because it is required by building regulations or guidance for buildings above certain heights or with particular layouts.
If you are refurbishing such a building you should understand:
- Whether the existing lift installation truly complies with the relevant firefighters lift standard for the era in which it was built
- What would be involved in modernising it to current expectations for a firefighters lift
- Whether it is feasible, from a building design and management point of view, to adapt or supplement it to provide evacuation lift capability
This is an area where a detailed survey and options study by a lift specialist such as Excel Lift Services, in conjunction with your fire engineer, is usually the most practical starting point.
3. Who will manage evacuation using lifts?
Evacuation lifts rely on effective management. Before committing to such a system you should be confident that:
- Your organisation can maintain trained staff or marshals to coordinate evacuation where required
- Personal emergency evacuation plans exist and are kept up to date for people who will need assisted or lift-based evacuation
- There are realistic arrangements for regular drills and familiarisation
- The system still functions safely at times of low staffing or out of hours
Technology can support evacuation but it cannot replace competent on-site management.
4. How will the lift be maintained and tested?
Both evacuation lifts and firefighting lifts need a higher level of assurance than ordinary passenger lifts. In practice this means:
- Planned preventative maintenance by a competent lift company with experience of life safety related lift systems
- Periodic testing of special modes, such as firefighters control, evacuation mode and automatic rescue operation, in coordination with building management and where appropriate the fire and rescue service
- Robust fault reporting and rectification processes, including knowing what to do if the evacuation lift or firefighters lift is temporarily out of service
Excel Lift Services can work with your responsible person or facilities team to develop maintenance and testing regimes aligned to manufacturers’ instructions, applicable standards and your fire strategy.
New build vs existing buildings
The opportunities and constraints can be very different between a new build and an existing structure.
New buildings
In a new project the architect, fire engineer, structural engineer and lift specialist can design the shaft, lobbies, safe areas, power supplies and control interfaces together. It is usually more straightforward to achieve full compliance with the latest editions of BS EN 81‑72 for firefighters lifts and BS EN 81‑76 for evacuation lifts.
There is also more flexibility to:
- Select locations and numbers of lifts for access, evacuation and firefighting
- Integrate smoke control and water management measures for the lift well from the outset
- Allow for future changes in occupancy or management
Existing buildings
Retrofitting an evacuation lift or upgrading to a modern firefighters lift in an existing building can be more challenging. Constraints often include limited shaft space, structural limitations and legacy fire protection or power routing.
However, there are still options in many cases, ranging from targeted modernisation of existing lifts to the creation of a new dedicated shaft. The viability and cost will depend heavily on the specific building and should be assessed on a case-by-case basis through surveys and feasibility studies.
Costs for a compliant evacuation lift or firefighters lift in the UK can vary widely depending on height, capacity, structural works, power arrangements and fire protection measures. A realistic budget is best developed once a concept design and survey are in place, and a bespoke quotation from a specialist is essential.
Common misconceptions
“Any lift with a fireman’s switch is a firefighting lift”
Older lifts sometimes have a simple fireman’s switch or recall feature. That does not make them full firefighters lifts in the BS EN 81‑72 sense.
A true firefighting lift requires specific shaft protection, lobby arrangements, power supply resilience, car features and controls as defined in the standard. A visual inspection alone may not reveal whether a lift meets the necessary criteria, so professional assessment is important.
“A normal passenger lift can double as an evacuation lift”
Ordinary passenger lifts are typically programmed to return to a designated floor and become unavailable to passengers when the fire alarm operates, in line with BS EN 81‑73. They are not designed or protected to carry passengers throughout a fire incident.
An evacuation lift must meet additional requirements for protection, control, power and integration into the evacuation plan. Simply changing the signage or programming on a standard lift will not make it a compliant evacuation lift.
“If we install a firefighting lift we do not need to plan for disabled evacuation”
A firefighters lift is primarily for the use of the fire and rescue service, not the general public. While firefighters may use the lift to rescue people once they have arrived and assessed conditions, you still need a clear strategy for how all building users, including those with mobility impairments, will reach a place of safety.
That strategy may or may not include an evacuation lift but the issue cannot be left to the fire service alone. The responsible person remains accountable under fire safety legislation for ensuring that suitable and sufficient arrangements are in place.
How Excel Lift Services can help
Choosing and configuring lifts that interact properly with your building’s fire precautions is a specialist task. It involves standards in the BS EN 81 series, national fire safety guidance, structural and architectural considerations and the realities of building management.
Excel Lift Services works with commercial building owners, developers and facilities managers across the UK to:
- Advise on lift options for new projects in the context of the overall fire and evacuation strategy
- Survey existing lifts and shafts to identify what is required to meet current expectations for firefighters lifts or evacuation lifts
- Design and install new lifts for commercial buildings, including lifts intended for use by the fire and rescue service or as part of managed evacuation plans
- Modernise key components of existing lifts to improve reliability, resilience and usability in fire conditions where appropriate
- Provide planned maintenance and responsive repairs to keep critical lift assets operating safely and in line with manufacturers’ instructions
Every building and fire strategy is different so there is no single right answer to the question of evacuation lift vs firefighting lift. In many cases you may need both capabilities in some form.